Name |
Value |
Supply voltage |
110 ± 33 V |
SB charger system |
Ug … 133 ± 2 V |
Maximum output current (Iout), max |
|
ЗУ 110/40 (5 design options) |
40, 50, 166 ± 1 A |
Setting for limitation of the storage maximum charge current, adjustable |
40, 50, 166 ± 1 A |
Current through temperature and current sensor: |
|
Long-term |
±50 А |
Maximum, measurable |
±60 А |
Maximum surge current (1s, duty cycle 1%) |
±600 А |
Built-in limitation of the charger starting current, max |
3 ± 1 А |
Work readiness time, max |
10 s |
Battery protection setting when discharging, adjustable |
0..145 ± 2 V |
Setting for switching on the "Low battery charge" (“АКБ разряж.”) indication, adjustable |
0..145 ± 2 V |
Voltage ripple factor on a resistive load, conversion frequency max |
±0.8% |
Time for single connection of the deeply discharged battery by pressing the “SB ON” (“ВКЛ. АКБ”) button |
10 min. |
Temperature sensor break indication |
Available |
Charge mode indication |
Available |
Battery protection contactor status indication |
Available |
Alarm indication |
Available |
Internal power modules operation indication |
Available |
Real time clock parameters registration: |
Available |
Supply voltage Ug |
|
Battery voltage Ub |
|
I battery charge/discharge |
|
Battery temperature |
|
Inside article temperature |
|
Article contactors condition |
|
“SB ON” (“ВКЛ.АКБ”) button condition |
|
Charger emergency protection against overheating |
Available |
Power input/output short circuit current protection |
Available |
Operating temperature |
-50 °С to +50 °С |
Service life |
20 years |
Protection level |
IP20 |
Unit weight, max (5 versions) |
14, 16, 18 ± 0.2 kg |
Overall dimensions (HxWxD) |
321 x 270 x 283 |
Structural design category |
М25 |