Name |
Value |
DC supply voltage value |
50 to 90 V |
Effective value of AC output voltage 50 Hz |
230 V (200-240 V) |
Output power |
800 VA |
Output voltage stabilization accuracy |
± 3 % |
Output voltage shape |
pure sinewave |
Rated output frequency |
50 Hz |
Output frequency stabilization accuracy |
± 0,5 % |
Output voltage THD |
|
At linear load |
1 % max |
At non-linear load |
4 % max |
Feedback |
“Power good” signal type “dry contact” or “open collector” |
Cross ratio |
3 : 1 |
Overload capability |
|
Up to 105 % |
Long-term |
105 % to 150 % |
5 s (with subsequent switching off) |
Efficiency |
87 % min |
External interface |
CAN (on/off, operating mode, errors) |
Remote switching on/off |
Digital signal 80 V |
Short circuit protection |
load trip |
Input pulse interference protection |
up to 450 V, 50± 1 μs |
Overheating protection |
yes |
Battery discharge protection |
On/off threshold is set |
Operating temperature |
-40 °С to +60 °С |
Service life |
20 years |
Protection level |
IP31 |
Unit weight |
4 kg, max |
Overall dimensions (HxWxD) |
80 х 332 х 200 |
Structural design category |
М25 |