| Name | Value |
|---|---|
| DC supply voltage value | 50 to 90 V |
| Effective value of AC output voltage 50 Hz | 230 V (200-240 V) |
| Output power | 800 VA |
| Output voltage stabilization accuracy | ± 3 % |
| Output voltage shape | pure sinewave |
| Rated output frequency | 50 Hz |
| Output frequency stabilization accuracy | ± 0,5 % |
| Output voltage THD | |
| At linear load | 1 % max |
| At non-linear load | 4 % max |
| Feedback | “Power good” signal type “dry contact” or “open collector” |
| Cross ratio | 3 : 1 |
| Overload capability | |
| Up to 105 % | Long-term |
| 105 % to 150 % | 5 s (with subsequent switching off) |
| Efficiency | 87 % min |
| External interface | CAN (on/off, operating mode, errors) |
| Remote switching on/off | Digital signal 80 V |
| Short circuit protection | load trip |
| Input pulse interference protection | up to 450 V, 50± 1 μs |
| Overheating protection | yes |
| Battery discharge protection | On/off threshold is set |
| Operating temperature | -40 °С to +60 °С |
| Service life | 20 years |
| Protection level | IP31 |
| Unit weight | 4 kg, max |
| Overall dimensions (HxWxD) | 80 х 332 х 200 |
| Structural design category | М25 |